The HYDROCAL 1008 Offshore is a permanently installed multi-gas-in-oil analysis system with transformer monitoring functions. It individually measures, Moisture in oil (H2O) and the key gases Hydrogen (H2), Carbon Monoxide (CO), Carbon Dioxide (CO2), Methane (CH4), Acetylene (C2H2), Ethylene (C2H4) and Ethane (C2H6) dissolved in transformer oil.
General
Optional nominal voltages of auxiliary supply:l |
120 V -20% +15% AC 50/60 Hz or 230 V -20% +15% AC 50/60 Hz or 120 V -20% +15% DC or 230 V -20% +15% DC Other nominal voltages on request! |
Power consumption: | max. 600 VA |
Housing: | Aluminium with painting C5M / stainless steel V4A |
Dimensions: | W 263 x H 274 x D 312 mm |
Weight: | Approx. 18 kg |
Operation temperature: (ambient) |
-55°C ... +55°C |
Oil temperature: (inside transformer) |
-20°C ... +90°C |
Storage temperature: (ambient) |
-20°C ... +65°C |
Oil Pressure: | up to 800 kpa (negative pressure allowed) |
Connection to valve: | G 1½" DIN ISO 228-1 or 1½" NPT ANSI B 1.20.1 |
Safety
Insulation protection: | IEC 61010-1:2002 |
Degree of protection: | IP-55 |