This website uses session cookies to provide the best possible functionality. Session cookies ensure that you are recognized when you move from page to page within our site and that any information you have entered is remembered. You can choose to accept cookies by changing the settings in your browser. For more information please refer to our Privacy Policy.

» PRIVACY POLICY
» CLOSE THIS BOX
Logo MTE Meter Test Equipment AG
MTE Meter Test Equipment AG
Logo MTE Meter Test Equipment AG
Logo MTE Meter Test Equipment AG

HYDROCAL 1011 genX

The new HYDROCAL 1011 genX is a full-range / maintenance-free multi-gas online DGA solution combining proven near infrared (NIR) measuring technology with miniaturized gas sample production based on headspace principle (no membrane, negative pressure-proofed). It individually measures Moisture in oil (H2O) and the key gases Hydrogen (H2), Carbon Monoxide (CO), Carbon Dioxide (CO2), Methane (CH4), Acetylene (C2H2), Ethylene (C2H4), Ethane (C2H6), Oxygen (O2), Nitrogen (N2) and Propane (C3H8) dissolved in transformer oil.

HYDROCAL 1011 genX animated
Technical information for HYDROCAL 1011 genX

Optional nominal voltages
of auxiliary supply:
120 V -20% +15% AC 50/60 Hz or
230 V -20% +15% AC/DC 50/60 Hz or
120 V +15% DC
Power consumption: max. 320 VA
Housing: Aluminium
Dimensions: W 270 x H 270 x D 333.5 mm
Weight: approx. 13.5 kg
Operation temperature:
(ambient)
-55°C ... +55°C
(below -10°C display function locked)
Oil temperature:
(in the transformer)
-20°C ... +120°C
Storage temperature:
(ambient)
-20°C … +65°C
Oil Pressure: 0 … 800 kPa
Connection to valve: G 1½" DIN ISO 228-1 or
1½” NPT ANSI B 1.20.1





© 2024 - MTE Meter Test Equipment AG