The new HYDROCAL 1011 genX is a full-range / maintenance-free multi-gas online DGA solution combining proven near infrared (NIR) measuring technology with miniaturized gas sample production based on headspace principle (no membrane, negative pressure-proofed). It individually measures Moisture in oil (H2O) and the key gases Hydrogen (H2), Carbon Monoxide (CO), Carbon Dioxide (CO2), Methane (CH4), Acetylene (C2H2), Ethylene (C2H4), Ethane (C2H6), Oxygen (O2), Nitrogen (N2) and Propane (C3H8) dissolved in transformer oil.
Optional nominal voltages of auxiliary supply: |
120 V -20% +15% AC 50/60 Hz or 230 V -20% +15% AC/DC 50/60 Hz or 120 V +15% DC |
Power consumption: | max. 320 VA |
Housing: | Aluminium |
Dimensions: | W 270 x H 270 x D 333.5 mm |
Weight: | approx. 13.5 kg |
Operation temperature: (ambient) |
-55°C ... +55°C (below -10°C display function locked) |
Oil temperature: (in the transformer) |
-20°C ... +120°C |
Storage temperature: (ambient) |
-20°C … +65°C |
Oil Pressure: | 0 … 800 kPa |
Connection to valve: | G 1½" DIN ISO 228-1 or 1½” NPT ANSI B 1.20.1 |