HYDROCAL 1003

The HYDROCAL 1003 is an online monitoring system permanently mounted on the transformer. It measures continuously Moisture in Oil (H2O) and the most important faults gases Hydrogen (H2) and Carbon Monoxide (CO).

Technical information for HYDROCAL 1003

Optional nominal voltages
of auxiliary supply:l
120 V -20% +15% AC 50/60 Hz or
230 V -20% +15% AC 50/60 Hz or
120 V -20% +15% DC or
230 V -20% +15% DC
Other nominal voltages on request!
Power consumption: max. 200 VA
Housing: Aluminium
Dimensions: W 224 x H 224 x D 307.5 mm
Weight: Approx. 7.5 kg
Operation temperature:
(ambient)

-50°C ... +55°C
(below -10°C display function locked)

Oil temperature:
(inside transformer)
-20°C ... +90°C
Storage temperature:
(ambient)
-20°C ... +65°C
Oil Pressure: up to 800 kpa
(NO negative pressure allowed)
Connection to valve: G 1½" DIN ISO 228-1
or
1½" NPT ANSI B 1.20.1