Logo MTE Meter Test Equipment AG
MTE Meter Test Equipment AG
Logo MTE Meter Test Equipment AG

HYDROCAL 1001+

The HYDROCAL 1001+ is a permanently-installed composite gas-in-oil sensor for the analysis of six dissolved key fault gases such as Hydrogen (H2), Carbon Monoxide (CO), Methane (CH4), Acethylene (C2H2), Ethylene (C2H4), and Ethane (C2H6). To detect an even wider range of potential transformer faults, the HYDROCAL 1001+ analyses additionally the content of Moisture (H2O) in the transformer oil.

Technical information for HYDROCAL 1001+

Optional nominal voltages
of auxiliary supply:l
120 V -20% +15% AC 50/60 Hz or
230 V -20% +15% AC 50/60 Hz or
120 V -20% +15% DC or
230 V -20% +15% DC
Other nominal voltages on request!
Power consumption: max. 250 VA
Housing: Aluminium
Dimensions: W 224 x H 195 x D 218 mm
Weight: Approx. 4 kg
Operation temperature:
(ambient)

-55°C ... +55°C
 

Oil temperature:
(inside transformer)
-20°C ... +90°C
Storage temperature:
(ambient)
-20°C ... +65°C
Oil Pressure: up to 800 kpa
(NO negative pressure allowed)
Connection to valve: G 1½" DIN ISO 228-1
or
1½" NPT ANSI B 1.20.1





© 2025 - MTE Meter Test Equipment AG