HYDROCAL 1008

The HYDROCAL 1008 is a permanently-installed multi-gas-in-oil analysis system with transformer monitoring functions. It allows for the individual measurement of Moisture in Oil (H2O) and the key gases Hydrogen (H2), Carbon Monoxide (CO), Carbon Dioxide (CO2), Methane (CH4), Acetylene (C2H2), Ethylene (C2H4) and  Ethane (C2H6) dissolved in transformer oil.

Technical information for HYDROCAL 1008



Optional nominal voltages
of auxiliary supply:l
120 V -20% +15% AC 50/60 Hz or
230 V -20% +15% AC 50/60 Hz or
120 V -20% +15% DC or
230 V -20% +15% DC
Other nominal voltages on request!
Power consumption: max. 600 VA
Housing: Aluminium
Dimensions: W 263 x H 274 x D 331 mm
Weight: Approx. 15 kg
Operation temperature:
(ambient)
-55°C ... +55°C
(below -10°C display function locked)
Oil temperature:
(inside transformer)
-20°C ... +90°C
Storage temperature:
(ambient)
-20°C ... +65°C
Oil Pressure: up to 800 kpa
(negative pressure allowed)
Connection to valve: G 1½" DIN ISO 228-1
or
1½" NPT ANSI B 1.20.1