This website uses session cookies to provide the best possible functionality. Session cookies ensure that you are recognized when you move from page to page within our site and that any information you have entered is remembered. You can choose to accept cookies by changing the settings in your browser. For more information please refer to our Privacy Policy.

» PRIVACY POLICY
» CLOSE THIS BOX
Logo MTE Meter Test Equipment AG
MTE Meter Test Equipment AG
Logo MTE Meter Test Equipment AG
Logo MTE Meter Test Equipment AG

HYDROCAL 1005

The HYDROCAL 1005 is a permanently-installed multi-gas-in-oil analysis system with transformer monitoring functions. It allows for the individual measurement of Moisture in Oil (H2O) and the key gases Hydrogen (H2), Carbon Monoxide (CO), Acetylene (C2H2) and  Ethylene (C2H4) dissolved in transformer oil.

Technical information for HYDROCAL 1005

Optional nominal voltages
of auxiliary supply:l
120 V -20% +15% AC 50/60 Hz or
230 V -20% +15% AC 50/60 Hz or
120 V -20% +15% DC or
230 V -20% +15% DC
Other nominal voltages on request!
Power consumption: max. 400 VA
Housing: Aluminium
Dimensions: W 263 x H 274 x D 331 mm
Weight: Approx. 13.5 kg
Operation temperature:
(ambient)
-55°C ... +55°C
(below -10°C display function locked)
Oil temperature:
(inside transformer)
-20°C ... +90°C
Storage temperature:
(ambient)
-20°C ... +65°C
Oil Pressure: up to 800 kpa
(negative pressure allowed)
Connection to valve: G 1½" DIN ISO 228-1
or
1½" NPT ANSI B 1.20.1