The HYDROCAL 1005 is a permanently-installed multi-gas-in-oil analysis system with transformer monitoring functions. It allows for the individual measurement of Moisture in Oil (H2O) and the key gases Hydrogen (H2), Carbon Monoxide (CO), Acetylene (C2H2) and Ethylene (C2H4) dissolved in transformer oil.
Optional nominal voltages of auxiliary supply:l |
120 V -20% +15% AC 50/60 Hz or 230 V -20% +15% AC 50/60 Hz or 120 V -20% +15% DC or 230 V -20% +15% DC Other nominal voltages on request! |
Power consumption: | max. 400 VA |
Housing: | Aluminium |
Dimensions: | W 263 x H 274 x D 331 mm |
Weight: | Approx. 13.5 kg |
Operation temperature: (ambient) |
-55°C ... +55°C (below -10°C display function locked) |
Oil temperature: (inside transformer) |
-20°C ... +90°C |
Storage temperature: (ambient) |
-20°C ... +65°C |
Oil Pressure: | up to 800 kpa (negative pressure allowed) |
Connection to valve: | G 1½" DIN ISO 228-1 or 1½" NPT ANSI B 1.20.1 |