The HYDROCAL 1005 Offshore is an online monitoring system permanently mounted on the transformer and is special designed for Offshore Wind Power Applications. It allows for the individual measurement of Moisture in Oil (H2O) and the key gases Hydrogen (H2), Carbon Monoxide (CO), Acetylene (C2H2) and Ethylene (C2H4) dissolved in transformer oil.
General
Optional nominal voltages of auxiliary supply:l |
120 V -20% +15% AC 50/60 Hz or 230 V -20% +15% AC 50/60 Hz or 120 V -20% +15% DC or 230 V -20% +15% DC Other nominal voltages on request! |
Power consumption: | max. 400 VA |
Housing: | Aluminium with painting C5M / stainless steel V4A |
Dimensions: | W 263 x H 263 x D 327.5 mm |
Weight: | Approx. 16.5 kg |
Operation temperature: (ambient) |
-55°C ... +55°C |
Oil temperature: (inside transformer) |
-20°C ... +90°C |
Storage temperature: (ambient) |
-20°C ... +65°C |
Oil Pressure: | up to 800 kpa (negative pressure allowed) |
Connection to valve: | G 1½" DIN ISO 228-1 or 1½" NPT ANSI B 1.20.1 |
Safety
Insulation protection: | IEC 61010-1:2002 |
Degree of protection: | IP-55 |