The new HYDROCAL 1006 genX is the first truly maintenance-free multi-gas online DGA solution combining proven near infrared (NIR) measuring technology with vacuum protected membrane extraction.
General
Optional nominal voltages of auxiliary supply:l |
120 V -20% +15% AC 50/60 Hz or 230 V -20% +15% AC 50/60 Hz or 130 V +15% DC |
Power consumption: | max. 240 VA |
Housing: | Aluminium |
Dimensions: | W 250 x H 250 x D 286 mm |
Weight: | Approx. 8 kg |
Operation temperature: (ambient) |
-55°C ... +55°C |
Oil temperature: (inside transformer) |
-20°C ... +105°C |
Storage temperature: (ambient) |
-20°C ... +65°C |
Oil Pressure: | up to 800 kpa (NO negative pressure allowed) |
Connection to valve: | G 1½" DIN ISO 228-1 or 1½" NPT ANSI B 1.20.1 |
Safety
Insulation protection: | IEC 61010-1 |
Degree of protection: | IP-55 |